Slots

Occupied slots2

Supply

Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power dissipation1.4 W
Power consumption1.4 W

Internal bus

Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit

Digital output

Number of channels2
Field device interface
Connectionchannel I: 1-2 NO; channel II: 3-4 NO; channel III: 5-6 NO; channel IV: 7-8 NO; channel V: 9-10 NO; channel VI: 11-12 NO; channel VII: 13-14 NO; channel VIII: 15-16 NO
Relay
Response time20 ms (depending on bus cycle time)
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication

Indicators/settings

LED indicationLED green: supply
LED red: communication fault
Codingoptional mechanical coding via front socket

Directive conformity

Electromagnetic compatibility

Conformity

Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2000
Environmental testEN 60068-2-14:2009
Shock resistanceEN 60068-2-27:2009
Vibration resistanceEN 60068-2-6:2008
Damaging gasEN 60068-2-42:2003
Relative humidityEN 60068-2-78:2001

Ambient conditions

Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3

Mechanical specifications

Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
ConnectionExe spring terminal with protective cover
Massapprox. 750 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)

Data for application in connection with hazardous areas

EU-Type Examination CertificateBVS 11 ATEX E 093 X
Galvanic isolation
Directive conformity

International approvals

ATEX approvalBVS 11 ATEX E 093X
INMETROBrazil: TUV 14.1599X
EAC approvalRussia: RU C-IT.MIII06.B.00129
Marine approval

General information

System informationThe module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the
Был online: Давно
OOO "ФилФар Технолоджи"
Рейтинг не сформирован
10 лет на Deal.by

Relay output FB6306B2

Под заказ
Цену уточняйте
Доставка
Оплата и гарантии